53
Displayed Alarm /
Warning
Device Description Recommended Actions
High product volume Tank The specied tank has reached
the programmed High Product
Volume.
Check product volume and compare to the programmed High Volume
alarm Limit in the setup menu. Acquire an accurate product level and
compare to the ATG. If levels differ, verify programming is correct. If
alarm persists, contact FFS Technical Services for support.
High High product volume Tank The specied tank has reached
the programmed High High
Product Volume.
Check product volume and compare to the programmed High High
Volume alarm Limit in the setup menu. Get an accurate product
volume and compare to the ATG. If levels differ, verify programming is
correct. If alarm persists, contact FFS Technical Services.
High water level Tank Water level exceeded High limit
set.
Verify programmed level. If water is too high consult you local site
policy procedures for corrective actions.
Level error Tank Product level exceeds tank
diameter due to an error in
console of programming.
Verify tank, offset, and probe programming.
Line monitor disabled Line Specied line is not enabled, so
line leak test will not be performed.
Verify line programming. If necessary enable line.
Low battery Tank Backup battery is low. See Installation Guide for replacement instructions.
Low product volume Tank/Manifold Product volume below Low limit
set. The tank / manifold specied
may be near empty
.
Acquire an accurate product volume. If actual product volume in
tank does not match the consoles displayed current volume, verify
programming.
Low low product volume Tank/Manifold Product volume below Low
Low limit. The tank or manifold
specied may be near empty.
Acquire an accurate product volume, and if does not match the
consoles displayed current volume, verify programming.
Mag installation error Sensor The specied TSP-DMS has an
installation error
Check the installation of the TSP-DMS, the sensor must be plumb.
If installation is correct, then try to relearn the sensor. If the problem
persist, the sensor may need to be replaced
Mag product alarm Sensor The specied TSP-DMS has
detected product.
Inspect the sump for the presence of product.
Mag sensor conguration
error
Sensor An error has been detected in the
conguration of the specied TSP-
DMS.
Enter into the setup and inspect the TSP-DMS setup.
Mag sensor data error Sensor There is an error with the reported
data from the specied TSP-DMS
Inspect wire connections at the Mag sensor. If the problem persists,
contact FFS Technical Services for support.
Mag sensor oat height
error
Sensor The oat height has exceeded the
limits as learned.
Inspect wire connections at the Mag sensor. If the problem persists,
contact FFS Technical Services for support.
Mag sensor oat missing Sensor The specied TSP-DMS is not
reporting the level information for
one or more oat.
Inspect the Mag sensor for damage and redo the connections. If the
Problem persists, contact FFS Technical Services.
Mag sensor missing Sensor The console is not receiving any
information from the specied
TSP-DMS.
Inspect wire connections at the Mag sensor. If the problem persists,
contact FFS Technical Services.
Mag sensor not learned
error
Sensor The specied TSP-DMS was not
properly learned.
Enter into the Control > Mag Sensor screen and have the console
learn the sensor.
Mag sensor
synchronization error
Sensor The console is receiving
incomplete or improperly timed
data from the specied
TSP-DMS
Inspect wire connections at the Mag sensor. If the problem persists,
contact FFS Technical Services.
Mag water alarm Sensor The specied TSP-DMS has
detected water.
Inspect the sump for water.
Mag water warning Sensor The TSP-DMS has detected water
above the preset limit.
Inspect the sump for water.
Manifold Delivery
Detected
Tank A delivery has been detected on
the specied manifold.
This is not an alarm and should only be a concern if there was not a
delivery to the site at the specied date and time.
Manifold Gross Leak
Detected
Tank A leak in the specied manifolded
tanks has been detected via a
SCALD test. Suspect possible
leak.
Review Tank Leak Test History and programming.
Refer to Section 5: Misc / Tank Leak Tests – Type and Frequency for
instructions on manually starting line leak tests.
Manifold Leak Detected Tank A leak in the specied manifolded
tanks has been detected via a
SCALD test. Suspect possible leak
Review Tank Leak Test History and programming.
Refer to Section 5: Misc/Tank Leak Tests – Type and Frequency for
instructions on manually starting line leak tests.
Manifold low product
volume
Tank The specied manifold has
reached the programmed Low
Product Volume
Check product volume and compare to the programmed Low Volume
alarm Limit in the setup menu. Acquire an accurate product volume
and compare to the ATG. If levels differ, verify programming is correct.
If alarm persists, contact FFS Technical Services for support.