Displayed Alarm /
Warning
Device Description Recommended Actions
VFM No Data VRM
The Vapor Flow Meter is detected
but is not communicating with the
Console
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Weekly Vapor Collection
Failure
VRM A Weekly Vapor Collection
Warning has occurred for 2
consecutive weeks.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Weekly Vapor Collection
Warning
VRM V / L average for Non-ORVR
transactions is greater than 1.32
or less than 0.81.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Warning
VRM Ullage pressure is greater than
+1.3” WC for 5% of time.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Failure
VRM A Weekly Ullage Pressure
Warning has occurred for 2
consecutive weeks.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Leak Test Failure
VRM The leak rate of the vapor
recovery system is two times the
allowable rate as stated in TP-
201.3 for one week.
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Weekly Ullage Pressure
Leak Test Warning
VRM A Weekly Ullage Pressure Leak
Test Warning has occurred for 2
consecutive weeks
Refer to Vapor Recovery Monitoring Alarm and Troubleshooting
identication guide 000-0529 for troubleshooting help.
Remote DTU is Ofine DTU The console cannot detect the
specied DTU.
Wrong ID Number
Dispenser Powered Off
Not installed correctly
Not on same phase voltage as console DTU
DTU FFS Interference DTU Two networks have the same
Network ID or nearby FFS
equipment is causing interference
with the system.
Verify Network ID programming in Setup Menu. DTU’s may be in
service at a nearby location that is causing interference. Contact
FFS Technical Services for support
DTU Non FFS
Interference
DTU Non-FFS equipment is causing
interference with the DTU signals.
Contact FFS Technical Services for support.
FMS Alarms
Alpha volume correction
error
Tank This error is caused by a
programming mistake in the
Special Products section.
Verify Special Product Alpha volume correction program parameters.
Contact FFS Technical Services Department for assistance.
API volume correction
error
Tank This error is caused by a
programming mistake in the
Special Products section.
Verify Special Product API volume correction program parameters.
Contact FFS Technical Services Department for assistance.
Correction table error Tank Level and Volume mismatch
detected in Correction table
programming.
Verify that all levels and volumes are entered accurately into the
Correction Table programming.
Density oat error Tank A communication error has
occurred involving the density
oat.
Verify programming and contact FFS Technical Services for support.
Density error Tank The density of the product is not
within specications.
Enter setup and verify the information under density in the probe
programming.
Float height error Tank This error could indicate that the
wrong oat type is installed or that
a programming error has occurred.
Review probe programming for proper oat type, number of oats in
the tank. (This would be an idea time to clean the probe and oats).
Float Missing Tank Probe detects a lesser number of
oats than programmed.
Review probe programming for correct number of oats. If correct
then inspect probe shaft, oats, and oat magnets. With the probes
out of the tank, this would be an idea time to clean the probe and
oats. If pressures meets requirements specied, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
FMS conguration error None Conicts exist within FMS
Application programming.
Verify FMS setting are correct in accordance with the site
specications.
High product level Tank Product level exceeded High limit
set. Possible close to tank overll
condition
Acquire an accurate product level. If actual product level in tank does
not match the consoles displayed current level, verify programming is
correct.
High high product level Tank Product level exceeded High High
limit set. Possible tank overll
condition.
Acquire an accurate product level. If actual product level in tank does
not match the consoles displayed current level, verify programming is
correct.