Programming Modules
The Fuel Management System is composed of a custom set of modules. Each module maintains individual characteristics.
Parameters must be set to match the site conguration. The programming table below will assist in this setup.
Remote Data Transfer Units (DTU’s)
Remote Data Transfer Units (DTU’s) are used in California for the purpose of relaying information from various sensors
mounted in dispensers to the FFS console.
Group Name Parameter Name
Parameter
Default
Description
Parameter
Input
Remote Data Transfer Units
Network ID (1) The I.D. of the network. #
Number of units (0) The number of DTUs in the eld. 1-16
DTU 1 Unit ID (0) Insert the Serial number of the rst DTU. abc#
For Further DIM or DTU Setup information, refer to the Web Browser Interface Section.
IO Modules
The Low Voltage Input / Output Module is a non-intrinsically safe module that provides eight separate AC or DC voltage inputs
that can range from 0 to 240 volts. In addition to the AC / DC inputs, the IO module also includes four 4-20mA signal outputs.
Group Name
Parameter
Name
Parameter
Default
Description Parameter Input
IO Modules
Module #
Inputs Channels (0) The number of A/C or D/C inputs physically wired to the gauge. 0-8
Channel #
Name (Input 1) Descriptive name used to identify the input. abc#
Enabled (Yes) Enables the input.
Yes / No
Active State (High)
High will activate channel when high voltage is present.
Low will activate channel with no voltage present.
High / Low
Action (None) Create an alarm or event timestamp . None
Alarm
Event
Outputs Channels (0) Number of 4-20mA channels in use per module. 0-4
Channel #
Name (output 1) Descriptive name used to identify the output
abc
Enable (Yes) Yes if the channel is in use
Yes / No
AC Input Modules
The AC Input Module is a non-intrinsically safe module that has 12 identical optically isolated AC input channels that can
be used for dispenser hook isolation, vapor processor input, or as generic AC inputs.
Group Name Parameter Default
Parameter
Default
Description
Parameter
Input
AC Input Modules
Number Gasoline Hooks per
Dispenser
(0)
Including diesel. This is for reference only
except on VRM applications.
0-8
Module # Channels (0) Number of channels in use per module. 0-12
Channel #
Name (AC Input 1) Given name of channel. abc#
Enabled (Yes) Yes if channel is used. Yes / No
Active State (High)
High will activate channel when high voltage
is present. Low will activate channel with no
voltage present.
High / Low
Action Setup None Create an alarm or event timestamp None, Alarm,
Event