48
TPI Setup
Group Name Parameter Name
Parameter
Default
Description Max Value
Power Supply
RS-485
TS-TPI
Enable Interface (Yes)
Enables TS-TPI options.
Yes/No
Controllers A* Number of Controllers (2) Number of controllers to be connected 31
Controller 1 Name Unlead Pump 1 Given Name of the pump controller abc#
Enabled (Yes) Enables the controller. Yes / No
Type (Mag/ECO)
Type of controller used
Variable Frequency
Smart
3 phase smart
Smart I
Mag / Eco
unknown
Address (1)
Unique address of the controller
30
Group (0)
Controller group number (if a member of a group)
15
Tank (1)
Tank associated with controller
48
Height (5.00 in)
Approximate distance of pump motor from tank
bottom
#
Number of Inputs (1) Number of inputs that will activate controller 32
Input 1
Type AC Input Module
Select module that contains the input
Modules listed
Channel Disp. 1/2 Unleaded
Specic input that will activate the controller
12
Controller 2
Name Unlead Pump 2
Given Name of the pump controller
abc#
Enabled (Yes)
Enables the controller.
Yes / No
Type (Mag/ECO)
Type of controller used
Variable Frequency
Smart
3 phase smart
Smart I
Mag / Eco
unknown
Address (1)
Unique address of the controller
30
Group (0)
Controller group number (if a member of a group)
15
Tank (1)
Tank associated with controller
48
Height (5.00 in)
Approximate distance of pump motor from tank
bottom
#
Number of Inputs (1)
Number of inputs that will activate controller
32
Input 1
Type AC Input Module
Select module that contains the input
Modules listed
Channel Disp. 1/2 Unleaded
Specic input that will activate the controller
12
* When in the Edit mode of Setup, an A will appear for AutoCongure. When the AutoCongure Option is used, the tank
gauge will locate all of the controllers that are properly wired in the system and identify them.
Note: All DIP switch settings for the FE Petro controllers should be set as stand alone controllers, with the exception of
the addressing. All controllers need to have a unique address that is NOT set to 0).