50
Displayed Alarm /
Warning
Device Description Recommended Actions
Console DTU is ofine Slot The Console DTU is not
communicating with the Console
Check for proper wire connection between the console and the
Console DTU. Verify DTU input power. Replace DTU
Console DTU number
mismatch
Slot
The number of DTU Modules
detected does not match the
number programmed.
Ensure that a console DTU is being used. Possible bad bus
connection. Not powered. Replace DTU if connections and settings
check good.
Controller Module is
Ofine
Slot Controller Module is ofine due to
unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady
try to reboot system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
DIM module number
mismatch
Slot DIM modules detected does not
match the number programmed.
Check that the number of DIM Modules installed matches the number
programmed under System Conguration > Modules Expected. If
problem persists, contact FFS Technical Services for support
Internal Error #1 System There is an internal buffer error
occurring in the gauge.
Contact FFS Technical Services for support
Invalid Conguration None The conguration that has been
loaded is not valid.
Verify the le type of the conguration which is being uploaded
Invalid Registration None The registration that is loaded is
not valid.
If you have upgraded the site before, use the upgrade tool to restore
the former registration. If you have not upgraded the site before,
contact FFS Technical Services for support.
IO Input Alarm None An input on the Input/Output
module has been congured as an
alarm and is active.
Check the programming and voltage inputs for the specied Input
channel on the IO module.
IO Module is ofine Slot The IO Module is not
communicating with the Console
Inspect the IO module for error lights. If green light is ashing,
recover the module. If the lights are off: Power down, remove / re-
seat the module and power back up. If problem persists, contact FFS
Technical Services for support
IO module number
mismatch
Slot IO Modules detected does not
match the number programmed.
Check that the number of IO Modules installed matches the num-
ber programmed under System Conguration > Modules Expected.
Check for a ashing green light or no light at all on the IO Module and
contact FFS Technical Services for support.
IS Barrier Violation None Non-Intrinsically Safe module
placed in IS area; or IS Barrier is
removed.
Check the module conguration to ensure that a module has not
been improperly placed. Power down and then remove / re-seat the IS
barrier. If problem persists contact FFS Technical Services for support
LON module number
mismatch
Slot Lon Modules detected does not
match the number of Lon Modules
programmed.
Check that the number of LON Modules installed matches the num-
ber programmed under System Conguration > Modules Expected.
If problem persists, contact FFS Technical Services for support.
Power Supply Input Alarm None An input on the Power Supply has
been congured as an alarm and
is active.
Check the programming and voltage inputs for the specied Low
Voltage Input channel on the Power Supply module.
Power Supply Module
number mismatch
Slot Power Supply Modules detected
does not match the number
programmed.
Check that the number of Power Supply Modules installed matches
the number programmed under System Conguration > Modules Ex-
pected. Check for a ashing green light or no light at all on the Power
Supply Module and contact FFS Technical Services for support
Power Supply Module is
Ofine
Slot Power Supply Module is ofine
due to unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady
try to reboot system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Services Dept. for support on this issue.
Power Supply Module
Setup Error
None Errors in the setup of the listed
module.
The console may need to be reprogrammed.
Printer Module Number
Mismatch
Slot Printer Modules detected does not
match the number programmed.
Check that the number of Printer Modules installed matches the
number programmed under System Conguration > Modules
Expected. If problem persists, contact FFS Technical Support.
Probe Module is Ofine Slot Probe Module is not
communicating with the console.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady,
re-seat module and reboot system. If the condition still exists, contact
Franklin Fueling Systems’ Technical Support for help on this issue.
Probe Module Number
Mismatch
Slot Probe Modules detected does
not match the number of Probe
Modules programmed.
Check that the number of Probe Modules installed matches the num-
ber programmed under System Conguration > Modules Expected.
Check for a ashing green light or no light at all on the Probe Module
and contact FFS Technical Services for support.
Probe Module Setup Error None Programming errors made during
setup of the Probe Module.
Verify Probe Module programming parameters. If the condition still
exists, contact Franklin Fueling Systems’ Technical Support for help
on this issue.
Relay Module is Ofine Slot Relay Module is ofine due to
unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady
try to reboot system. If the condition still exists, contact Franklin
Fueling Systems’ Technical Support for help on this issue.