Fuel Management SystemProgramming GuideT5 SeriesSoftware Revision 1.7.4 Franklin Fueling Systems • 3760 Marsh Rd. • Madison, WI 53718 USATel: +1 608
6Password Login1. Press the User Roll icon 2. Enter Password for the desired level as described in the Access Control section on page 5.Default pas
7Conguring IP Settings for CommunicationBefore attempting to modify any computer settings, contact the Information Technologies department of your bu
8• In Classic View, click on Network Connections.4. Right-click on Local Area Connection and select Properties.5. In the Local Area Connection Prope
9Obtain an IP Address AutomaticallyComputers commonly use this setting to obtain an IP address automatically. 1. If Obtain an IP address automaticall
10Connecting a PC to the T5 series RS-232 PortCOMM 1 is used to connect a PC or laptop with the console via the Web Browser Interface for programming
115. Enter a Computer Name (it can be the site name).6. Select the communication port to be used from the Select a Device drop-down list.7. Select
1210. Under the General tab, select Congure. 11. Change the Maximum speed (bps) to 57600.12. Disable all of the Hardware Features and click OK.13.
1319. In the Type of dial-up server I am calling, select PPP: Windows 95 / 98 / NT4 / 2000, Internet from the drop-down list then click OK.Check Oper
14Conguration and PreferencesConguration and Preferences include how information will be displayed and conguring the console for its location and c
15Numbers OptionsDigit groupingGroup digits by 103 using specied symbol (i.e. either “123456789” or “123,456,789”).Digit grouping symbol Symbol used
iiCopyright ©2011 by Franklin Fueling Systems. No part of this publication may be reproduced in any form without the prior written consent of FFS. All
16Conguration MenuConguration OptionsUsing the options in this menu, you can change:• Console passwords • COM 1 parameters• Network parameter
17Time ZoneSet the Time Zone according to your geographical location. If your choice does not appear on the rst screen, use the navigation up and dow
18Programming and NavigationConsole NavigationThe operating system is designed for easy navigation. Applications allow the user to modify programming
19Character Navigation ButtonsWhen prompted to enter system information, press the corresponding keys.Character Selection: Selects between upper case
20Programming System ParametersUsing the touch screen function of the console to program, navigate from the Home Status screen by pressing the Main Me
21Programming ModulesThe Fuel Management System is composed of a custom set of modules. Each module maintains individual characteristics. Parameters m
22Probe ModulesThe Probe Module gather data from probes, vapor ow meter and TS-DMS sensors. This information is processed by the Controller Module fo
234-20 mA and 4-20 mA EXP Input Modules The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface. The 4-
24Power Supply ModuleThe Power Supply is a non-intrinsically safe module that provides power to the T5 series console from line voltage rated 110 - 24
25Group Name Parameter NameParameter DefaultDescriptionParameter InputRS-232 Baud Rate (9600) Data transmission speed in bits per second. 1200-5760
iiiContentsNotice...iiI
26Relay ModulesThe Relay Module is a non-intrinsically safe module that has 8 identical Form C output channels. Each channel has a fuse and three term
27Dispenser InterfaceThe Dispenser Interface is used in VRM and Reconciliation applications to communicate sales data from the dispensers to the conso
28Programming FMS ParametersHere is where specic equipment parameters will be modied to match the site setup.Fuel Management SystemGroup Name Parame
29FMS Parameters ContinuedGroup Name Parameter NameParameter DefaultDescriptionParameter InputFuel Management System Special Tanks Special # Sh
30Group Name Parameter NameParameter DefaultDescriptionParameter InputSpecial ProductsSpecial NCorrection Type (Table 6A) As dened by the fuel provid
31Group Name Parameter NameParameter DefaultDescriptionParameter InputReconciliationOver Short Limit Percent (1.00%) Gives the allowed amount on varia
32E-MailGroup Name Parameter NameParameter DefaultDescriptionParameter InputE-Mail “From” [email protected] of sender (console)
33Web Browser InterfaceNavigating Applications RemotelyThe Web Browser Interface offers several ways to navigate through applications: • Easy-to-rea
34Backup Setup FilesDownloadBackup allows you to download the setup le and store it on any PC connected to the console. This le can be uploaded to t
35UploadWhen required, the backup conguration le will need to be reloaded onto the console to restore a previous setup. When uploading, it is import
ivProgramming Parameters ... 28Fuel Manage
36Leak TestingAll T5 series console models meet (or exceed) the requirements of the U.S. Environment Protection Agency (EPA / 530 / UST-90 / 006 test
37Manually Forcing Static Leak Tests1. To force a Static Tank Leak test, press the FMS button in the Application Window.2. Press the Application Men
38Tank Leak Test ResultsLeak test results are either increase, passed, failed, or indeterminate.Reasons Why Tank Leak Tests Fail• The tank leaks.•
39TS-LS500 Auto Learn Line Leak TestingOverviewA 0.2 gph and a 0.1 gph test line leak tests can be started from the console. Some jurisdictions recomm
40DTU (Data Transfer Unit) Setup and Programming1. Under Setup / System Conguration/Modules Expected, set Console DTU to 1.2. Under Setup, locate R
419. Under Setup/4-20mA Input Modules (DTU) / locate Remote Module 2 and enter the number of DTUs installed. The maximum number of channels per a 4-2
42DIM Programming1. For Web Browser programming capability, connect a computer to the T5 series tank gauge. (See programming section of this manual f
4311. Communication refers to the method of communication used by the corresponding distribution box.Some typical examples:• Current loop-Gilbarco P
4415. Under Dispenser Interface, select Fueling Points.Note: A Fueling Point is anywhere a vehicle can stop and dispense fuel. Most dispensers have
45There are two ways to program the Hose Position:• Manually-If you know the D-Box grade position you can manually select the Position number from th
1Important Safety MessagesFFS equipment is designed to be installed in association with volatile hydrocarbon liquids such as gasoline and diesel fuel.
46Dual DIM InstallationSome sites and dispenser congurations may require the use of a second DIM module that would be installed externally to perform
47TS-TPI Overview and Functionality Tank fuel management can be achieved using a Franklin Fueling Systems T5 Series Fuel Management Systems and an
48TPI SetupGroup Name Parameter NameParameter DefaultDescription Max ValuePower Supply RS-485TS-TPIEnable Interface (Yes)E
49List of Alarms and TroubleshootingFor all alarms conditions, the troubleshooting steps provided in this chapter are suggested actions to take in the
50Displayed Alarm / Warning Device Description Recommended ActionsConsole DTU is ofine Slot The Console DTU is not communicating with the ConsoleChe
51Displayed Alarm / Warning Device Description Recommended ActionsRelay module number mismatchslot Relay Modules detected does not match the number pr
52Displayed Alarm / Warning Device Description Recommended ActionsVFM No Data VRMThe Vapor Flow Meter is detected but is not communicating with the Co
53Displayed Alarm / Warning Device Description Recommended ActionsHigh product volume Tank The specied tank has reached the programmed High Product V
54Displayed Alarm / Warning Device Description Recommended ActionsManifold low low product volumeTank The specied manifold has reached the programmed
55Displayed Alarm / Warning Device Description Recommended ActionsSCM AlarmsContainment Not Learned SCM The learning process has not been completed.Re
2Certied Programmer/Service Person: Only an FFS certied programmer or service person is allowed to access both the user interface keypad and areas i
56Displayed Alarm / Warning Device Description Recommended ActionsSN3 Pwr Short Slot 3-Wire sensor malfunction. If a 2-Wire sensor is used on a 3-wire
57Displayed Alarm / Warning Device Description Recommended ActionsLine Not Learned Line Specied line not learned. Complete learn process, if any lear
58Displayed Alarm / Warning Device Description Recommended ActionsPump Communication Fail TPI Communication from the TPI to the STP controller has fai
59Appendix A - Standard Tanks TableLegendO/C = Owens Corning / FC Fluid ContainmentD = Diameter (Dia.)L = LengthS = Single WallDW = Double Wall Tank (
60Type #Manufacturer Model Capacity (Gallons)DimensionsD x L (inches)S / DW Wall27 Xerxes — 3,000 96 x 147 S28 Xerxes — 4,000 75 x 263 S29 Xerxes —
61Appendix B - Standard Products Table Product Name API Gravity (6B Compensation)Leaded Regular 63.5Unleaded Regular 63.5Unleaded Plus 62.8Unleaded Ex
©2011 FFS 000-2142 Rev. E
3IntroductionThe purpose of this manual is to guide installers, operators and technicians through programming and troubleshooting the T5 series consol
4Denitions and AcronymsModule – A module is a plug-in card within the T5 series console that is used to perform various functions of the console. The
5GeneralAfter the Fuel Management System has been installed, typically your interaction with the system will be from the LCD display, on-board printer