23
4-20 mA and 4-20 mA EXP Input Modules
The Analog Input Module has 8 identical channels for loop powered IS sensors with a 4-20 mA interface.
The 4-20 mA EXP module is programmed in the same manner. The 420 EXP module is located on the hazardous side of
the console, must have the wires enclosed in explosion-proof conduit, and has a red front. If a DTU is being used there
will be an option for a “virtual module” labeled Remote Module. The Remote Module gathers information from the vapor
pressure sensor when a DTU is used. (see DTU Programming for further details on page 31 in this manual.)
Group Name
Parameter
Name
Parameter
Default
Description Parameter Input
4-20mA Input Modules
Module # Channels (0) Number of channels in use per module. 0-8
Channel #
Name (4-20mA Input 1) Given name of the channel. abc#
Service Type (Analog) Determines the input signal.
Analog
Secondary Containment Monitoring
Line Leak Detection
Vapor Recovery Monitoring
FMS Level Probe
Low Range -8.00 Low range of mA input - #
High Range 8.00 High range of mA input + #
#3 Remote
Module 2 (DTU)
Channels (0) Number of channels in use 0-5
Name 4-20 mA input 6 Given name of the channel abc#
Service Type (Vapor Recovery) Determines the output signal Vapor Recovery Monitoring