32
E-Mail
Group Name Parameter Name
Parameter
Default
Description
Parameter
Input
E-Mail
“From” Address
your_from@address.
com
Address of sender (console). abc
SMTP Host
your_smtp_host_
address
IP address of SMTP Host. #
SMTP Port 25 Port address of SMTP. #
Enable Authentication No Data authentication (if required). Yes / No
Maximum Queue Size 20 Maximum size of queue in Megabytes.
Retry Timeout 3600 Time, in seconds, that the console will wait before attempting
to resend the message.
Watchdog Timeout 30
Time, in seconds, that the console self-monitoring program
waits when it expects and error due to software or power
quality problems.
Enable Debugging (No) Select Yes if you would like more status information to be
stored in the Messages le.
Yes / No
System Sentinel Anyware
This section will be lled out automatically upon the initial polling by System Sentinel Anyware.
Events
Group Name Parameter Name Parameter Default Description Options
Rules: Rules are a logic-based programming that are driven off of “If” based Events and “Then” Based actions. Essentially: “If” this event occurs
“Then” the console will perform a specied action.
Rule – New Rule #
Name (New Rule #) Given name of rule. abc#
Enabled (No) Yes to enable rule. Yes/No
Events: Events can be both “If” logic and “Or” Logic. Therefore you can have several events trigger the same action. “If” Event 1 “Or” Event 2
occurs the console will perform a specied action.
Event
Type (New Alarm Occurred) Event type that triggers action. New Alarm Occurred;
Alarm Status Changed;
Application Event;
Scheduled
Category (Any) System that event occurs in to trigger
action.
Any;
System;
FMS;
VRM;
SCM;
Other
Code (Any) Error/Trouble Event Code that triggers
action.
(see below)
Device (Any) Device that created the alarm
condition.
Various
State (Any) State of alarm to trigger action. Various
Action: Actions are sequentially “Then” / ”And” driven. Therefore, “If” an Event occurs “Then” the console will perform Action 1 and then Action
2 and then Action 3.
Action Type (e-mail) Action that will occur upon event E-mail, Report, Relay, Tank
Testing, Line Testing, Sentinel
mode, Reconciliation, sound,
Notify SSA, Sample input,
STP Control, Generator
Address your,[email protected] Where it will send e-mail
Contact Generated What e-mail format is used Generated, Text, HTML, Other
Template Text E-mail Template HTML, Text, short text
Vista de página 35