39
Displayed Alarm /
Warning
Device Description Recommended Actions
Low battery Tank Backup battery is low. See Installation Guide for replacement instructions.
Low low product volume Tank/Manifold Product volume below Low
Low limit set. The tank or
manifold specied may be
close to empty.
Acquire an accurate product volume. If actual product volume in
tank does not match the consoles displayed current volume, verify
programming.
Low product volume Tank/Manifold Product volume below
Low limit set. The tank or
manifold specied may be
close to empty.
Acquire an accurate product volume. If actual product volume in
tank does not match the consoles displayed current volume, verify
programming.
Manifold Gross Leak
Detected
Manifold A Gross leak is detected in
the specied manifold
Review tank leak test history and programming. Refer to Section
5: Misc./ Tank Leak Tests – Type and Frequency for instructions on
manually starting line leak tests.
Manifold Leak Detected Manifold A leak is detected in the
specied manifold
Review tank leak test history and programming. Refer to Section
5: Misc./ Tank Leak Tests – Type and Frequency for instructions on
manually starting line leak tests.
Manifold SCALD Leak
Detected
Manifold SCALD software detected
a leak in the specied
manifold.
Review tank leak test history and programming. Review, why tank tests
fail.
Manifold Theft Detected Manifold Product used in Sentinel
Mode exceeds theft limit
set.
Verify theft limit in programming. Also obtain an accurate product level
and compare to inventory.
Marginal Pass of Gross
Leak Test
Line Gross test passed with
marginal results. May
be caused by thermal
instability of the line or a
leak.
Engineering
Modem Error None Indicates that a modem
malfunction has occurred.
Try to recycle power on the console. Verify modem programming. If
the alarm does not clear, contact Franklin Fueling Systems’ Technical
Services Dept. for support on this issue.
Monthly Leak Test Failed Line 0.2 GPH Line leak test
failed.
Follow site policy on line leak procedures.
Net error Tank Product net level exceeds
tank diameter due to
misconguration of
programming.
Verify tank, offset, and probe programming.
No data available Tank Engineering Engineering
No probe detected Tank Communications error
between probe and
console.
Verify correct probe programming. If problem still exists, suspect wiring
or faulty probe head.
Not Enabled Line Specied line not enabled. Verify programming.
Not Learned Line Specied line not learned. Verify programming. If necessary to learn line see TS-5 Series FMS
Installation Manual for TS-Ls500 AutoLearn Calibration instructions.
Open analog input Tank No analog input signal. Verify programming, if alarm is still present check wiring. If problem still
persists, suspect analog module to be at fault.
Power Supply Module is
Ofine
Slot Power Supply Module is
ofine due to unknown
causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady
try to reboot system. If the condition still exists, contact Franklin Fueling
Systems’ Technical Services Dept. for support on this issue.
Power Supply Module
Setup Error
None Errors in the setup of the
listed module.
The console may need to be reprogrammed.
Precision Leak Test Failed Line 0.1 GPH Line leak test
failed.
Follow site policy on line leak procedures.
Pressure Transducer Fail Line Leak Sensing Unit
(Transducer) sending
erroneous data to console.
Only FFS AutoLearn TS-Ls500 Transducers can be used with this
system for line leak detection. Verify line leak programming. Check
wiring continuity from LSU to console. If the condition still exists, contact
Franklin Fueling Systems’ Technical Services Dept. for support on this
issue.
Printer Paper Jam None Indicates that paper is
jammed in printer.
Carefully lift printer cover to inspect and remove the jammed paper.
Probe Module is Ofine Slot Probe Module is ofine due
to unknown causes.
Follow safety procedures before working inside the console. Visually
verify a steady green “Run” light. If red “Err” light is ashing or steady
try to reboot system. If the condition still exists, contact Franklin Fueling
Systems’ Technical Services Dept. for support on this issue.